OPGW with PBT Tube

- Features

Detail

Technical Specifications

    Yam No Yam No Material Dia.
  Fiber G.652D to 96 Cores SM or MM 0      
  Center AL-Tube 1     Tube-Dia. 6.2/9.7 mm
Structure Layer 1 20.3% AS wire 7 40% AS wire 4 Diameter 3.70 mm
                 
                 
                 
                 
  According to IEC, IEEE, DL/T 832-2003, GB/T 7424.4-2003 standards    
  Stranding direction of outer layer is right hand(Z-stranding)      
  Cable Diameter         17.1 mm
  Cable Weight         850 kg/km
  Supporting Cross Section         162.0 mm2
    Section of AS Wire 118.27 mm 2      
    Section of AA Wire 0.00 mm 2      
    Section of AL tube 43.71 mm 2      
  Rate Tensile Strength (RTS)       120.0 kN
Technical Data Modulus of Elasticity (E-Modulus)       119.3 kN/ mm2
  Thermal Elongation Coefficient       14.9 ×10 -6 /℃
  Permissible Maximum Working Stress (40% RTS)     296.4 N/ mm2
  Everyday Stress(EDS) (16%~25% RTS)   118.6 ~185.2 N/ mm2
  Ultimate Exceptional Stress (70% RTS)     627.9 N/ mm2
  DC Resistance         0.294 Ω/km
  Short Time Current   (0.3s, 20℃~200℃)     25.1 kA
  Short Time Current Capacity I 2 t       188.3 kA 2 s
  Minimum Bending Radius: Installation:     342 mm
      Operating:     256 mm
Temperature Installation         -10℃ ~ +50
Range: Transportation and Operation       -40℃ ~ +80

All Sizes and values are nominal
Diameters Tolerance: +/-2% / Weight Tolerance: +/-2%

 

Types of fibers available

    • Singlemode: G652D
    • G655 singlemode ,  NZDS (Non Zero Dispersion Shifted) fibers
    • Multimode OM2
    • Multimode OM3

Applications

  • Aerial facilities
  • High voltage distribution lines
  • Medium voltage distribution lines

Quality

There are different series of tests to ensure the quality of OPGW:

  • Routine testing  (testing in progress according to the internal quality plan)
  • Factory Acceptance Test  (FAT, witnessed by the customer)
  • Type testing  (only in case of a new basic design, repetition in exceptional cases)

OPGW testing must be in accordance with applicable standards or agreements between the purchaser and the manufacturer. As a general rule, testing will be performed in accordance with IEC 60794-4-10. However, if necessary, testing can be performed in accordance with IEEE Std 1138.

Type testing  may be waived upon presentation of the manufacturer's certificate for the similar product, which has been carried out by an independent testing organization or internationally recognized laboratory. If type testing must be carried out, it shall be carried out in accordance with an additional type testing procedure agreed upon between the purchaser and the manufacturer.

Routine Testing The optical attenuation coefficient for all production cable lengths is measured according to IEC 60793-1-CIC (backscattering technique, OTDR). Standard single-mode fibers are measured at 1310nm and 1550nm. Non-zero dispersion single-mode (NZDS) fibers are measured at 1550nm.

Factory  acceptance testing is carried out on two samples per order in the presence of the customer or their representative. The requirements for quality characteristics are determined by the relevant standards and agreed quality plans.

Installing OPGW requires some additional planning, as it's impractical to splice an OPGW cable mid-span; purchased cable lengths must be coordinated with the spans between towers to avoid waste. When fibers must be joined between lengths, a weatherproof splice box is installed on a tower; a similar box is used to transition from the OPGW to a single-fiber cable plant to connect the fibers to terminal equipment.